CVE-2025-27256
Missing Authentication for Critical Function vulnerability in GE Vernova Enervista UR Setup application allows Authentication Bypass due to a missing SSH server authentication. Since the client connection is not authenticated, an attacker may perform a man-in-the-middle attack on the network.
An attacker may perform a Man-in-the-middle attack on the network in order to steal credentials or forge malicious traffic
March 7, 2025
This issue affect the GE Vernova EnerVista UR Setup software from version 7.0 to 8.60
CVE-2025-27256
CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:L/I:H/A:H
8.3
Update the EnerVista UR Setup software to the latest released version
Diego Giubertoni of Nozomi Networks
Nozomi Networks Labs curates threat and vulnerability insights that are continuously fed into the Nozomi Networks platform to ensure our sensors can detect existing and emerging threats and vulnerabilities that threaten customers environments.